3.850₫
Hải Phòng, Việt Nam
Liên hệ: Ms Tươi
ĐT/Zalo: 0378722487
Gmail: nguyentuoi.longgiang@gmail.com
| General specifications | ||
|---|---|---|
| Switching function | Normally open/closed (NO/NC) | |
| Output type | Two-wire | |
| Rated operating distance | 40 mm | |
| Installation | non-flush | |
| Output polarity | AC/DC | |
| Assured operating distance | 0 ... 32.4 mm | |
| Actual operating distance | 36 ... 44 mm typ. 40 mm | |
| Reduction factor rAl | 0.37 | |
| Reduction factor rCu | 0.3 | |
| Reduction factor r304 | 0.73 | |
| Reduction factor rFe | 1 | |
| Reduction factor rBrass | 0.4 | |
| Output type | 2-wire | |
| Nominal ratings | ||
| Switching frequency | 0 ... 25 Hz | |
| Hysteresis | 1 ... 10 typ. 5 % | |
| Reverse polarity protection | reverse polarity tolerant | |
| Short-circuit protection | pulsing | |
| Voltage drop | ≤ 5 V (typ. 2V) DC operation ≤ 8 V (typ. 3 V) AC operation | |
| Momentary current (20 ms, 0.1 Hz) | 0 ... 3000 mA | |
| Operating current | 5 ... 500 mA | |
| Rated operating current | 500 mA 50/60 Hz | |
| Lowest operating current | 5 mA | |
| Off-state current | ≤ 1.5 mA | |
| Usage category | AC12 , AC140 , DC12 , DC13 | |
| Time delay before availability | ≤ 300 ms | |
| Operating voltage indicator | LED, green | |
| Switching state indicator | LED, yellow | |
| Error indicator | flashes when overcurrent | |
| Functional safety related parameters | ||
| MTTFd | 550 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Electrical specifications | ||
| Rated operating voltage | 24 ... 250 V DC / 24 ... 230 V AC | |
| Operating voltage | 20 ... 275 V DC / 20 ... 253 V AC | |